Leave Your Message
CQB3-63 series 50Hz/60Hz AC Miniature Circuit Breaker
Miniature Circuit Breakers

CQB3-63 series 50Hz/60Hz AC Miniature Circuit Breaker

CQB3-63 series miniature circuit breakers are suitable for protection of distribution lines with AC 50Hz (or 60Hz), rated working voltage 230/400V, rated current up to 63A, and rated short-circuit breaking capacity not exceeding 6000A. They are used for infrequent connection, disconnection and conversion of lines, and have overload, short-circuit and isolation protection functions. They can be widely used in terminal distribution application scenarios in various industries such as construction, new energy, electricity, and infrastructure.

    Overview and applications

    The CQB3-63 series miniature circuit breaker, crafted by CHAC Electric, is designed to fulfill the customization needs of international clients in low - voltage electrical systems. As a professional contract manufacturer with extensive export experience, we excel in ODM/OEM services.

     

    Our CQB3-63 series highlights advanced technology and strict quality control. Leveraging cutting - edge equipment and stringent quality standards, we guarantee reliable performance. We understand international clients' unique requirements and offer flexible customization from product design to packaging. Our efficient processes and quality systems ensure timely delivery of high - quality products, empowering clients to thrive in the global market.

     

    1.Wide-frequency compatibility

    2.High voltage/current

    3.High breaking capacity

    4.High Interruption rating capabilities.

    5.Overload & short circuit protection

    6.Positive isolation

    Suitable for industrial, commercial, high-rise and civil residences circuit protection.

    Technical data

    Specifications
    Insulation voltage 500V
    Rated impulse withstand voltage Uimp 4000V
    Rated current(A) 6、10、16、20、25、32、40、50、63
    Rated frequency 50Hz/60Hz
    Number of poles 1P、1P+N、2P、3P、3P+N、4P
    Rated breaking capacity Icn=lcs(A) 6000A
    Mechanical & Electrical life Mechanical≥10000,Electrical≥6000
    Tripping curves B、C、D
    Grid distance 45mm
    Protection class IP20
    Standards IEC60898-1、GB/T10963.1
    Tripping curves CCC

    Table1 Tripping characteristics (Reference temp.30°C)

    Item Type Test current
    In(A)
    Initial Status Time limit for tripping or
    non-tripping
    Expected result Remarks
    a B、C、D 1.13ln Cold t≤1h Non-tripping Current smoothly rises to specified value in 5s
    b B、C、D 1.45ln Following
    previous test
    1h Tripping
    c B、C、D 2.55ln Cold 1s<t<60s(In≤32A)
    1s<t<120s(In>32A)
    Tripping
    d B 3ln Cold t≤0.1s Non-tripping Switch on the power supply by closing the auxiliary switch
    C 5In
    D 10In
    e B 5In Cold t<0.1s Tripping Switch on the power supply by closing the auxiliary switch
    C 10ln
    D 20ln

    Note: The term "cold" means that the test is carried out at a reference calibration temperature without load before the test.

    Tripping curves

    Tripping-curves.jpg

    Conductor requirements and cross section

    Copper cross-section(mm²) Rated current In(A)
    1 In≤6
    1.5 6<In≤13
    2.5 13<In≤20
    4 20<In≤25
    6 25<In≤32
    10 32<In≤50
    16 50<In≤63

    Dimensions (unit:mm)

    Dimensions.jpg

    Order Specifications

    1.When ordering circuit breakers, the following points should be specified:

    A) Product models, such as CQB3-63;

    B) Poles of circuit breakers, such as 1P、1P+N、2P、3P、3P+N、4P;

    C) Types of instantaneous tripping,such astype B/C/D;

    D) Rated current of circuit breakers, such as 16A、20A、25A;

    E) Order quantity,such as100pcs

    2.Purchase order template

    CQB3-63 2P C/16A 100pcs

    Leave Your Message

    Send Inquiry

    The service network covers more than 50 countries and regions