1. Application

Safe and reliable electric energy allocation, continuity and control for industrial , construction and machinery manufacturing. Innovative protection concepts, and communication functions with fault diagnosis.


Features

· Compact structure, standard type(L type) and higher type( M type)

· Electric ratings: AC 400V ,50Hz/60Hz

· Up to 800A current rating

· Mounting mode: Vertical and horizontal

· Compliant standard: IEC/EN60947-2.

· High interruption, short arc (partial zero arc) and anti-vibration.


2. Selection

For example, if you order CQM3-125, standard type, three-pole, distribution, rated current 50A with 2 shunt tripper and front panel wiring , that is, to order CQM3-125L/3310 50A, qty:2.


3. Technical data

Frame rated current
In(A)

63

125

250

400

800

Model

CQM3-63L

CQM3-63M

CQM3-125L

CQM3-125M

CQM3-250L

CQM3-250M

CQM3-400

CQM3-800

Poles

3/4

3/4

3/4

3/4

3/4

Nominal current In(A)

16/20/25/
32/40/50/63

16/20/25/32/
40/50/63/80/100/125

100/125/160/
180/200/225/250

200/225/250/315/
350/400

400/500/630/
700/800

Rated insulation voltage Ui(V)

AC800

AC800

AC800

AC800

AC800

Rated impulse withstand voltage Uimp(V)

8000

8000

8000

8000

8000

Rated operational voltage Ue(V) 50Hz/60Hz

AC400

AC400

AC400

AC400

AC400

Arcing distance

≯50(mm)²

≯50(mm)²

≯50(mm)²

≯100(mm)²

≯100(mm)²

Rated breaking capacity Icu(kA)

L:35

M:50

L:35

M:70

L:35

M:70

70

75

Rated service short circuit breaking capacity Ics(kA)

L:25

M:35

L:25

M:50

L:25

M:50

50

50

Utilization class

A

A

A

A

A

Electrical life(cycles)

8000

8000

8000

7500

7500

Mechanical life(cycles)

Without maintenance

20000

20000

20000

10000

10000

With maintenance

40000

40000

40000

20000

20000

Overall Dimensions (mm)

width

78/100

92/122

107/142

150/198

210/280

Length

135

150

165

257

280

height

82

86

103

107

115.5


Note:

1: According to the IEC60947-1 term "life" denotes the probability of the number of operating cycles that an electrical appliance completes before repairing or replacing components.

2: Zero flying arc cover with height of 4mm (CQM3-63L/M,), 6.2mm CQM3-100L/M, 7.5mm (CQM3-250L/M), 9.3mm (CQM3-400L/M, CQM3-630L/M) and 9.5mm (CQM3-800L/M) is selected to realize zero flying arc.


4. Dimensions(unit :mm)

Model

Poles

Overall Dimensions

Mounting dimensions

A

B

C

D

a

b

φd

CQM3E-63

3

78

135

98.5

82

25

117

3.5

4

100

50

CQM3E-125

3

92

150

104

86

30

129

4.5

4

122

60

CQM3E-250

3

107

165

127

103

35

126

5

4

142

70

CQM3E-400

3

150

257

147

107

44

194

7

4

198

88

CQM3E-800

3

210

280

155

115.5

70

243

7

4

280

140


5. Certificate