1. Overview

CAB30aL-40 Residual Current Breakers with Overload Protection RCBo is be used for protection against overload and short-circuit currents; protection against the effects of sinusoidal alternating and direct pulsating earth fault currents; protection against indirect contacts and additional protection against direct contacts; command and isolation of resistive and inductive loads. Suitable for commercial and industrial applications.

The product is conformity with GB16917.1, IEC61009-1 standards.


2. Type designation


3. Technical data

Model

Versions

Rated voltage(v)

230V~

Rated current(A)

6A、10A、16A、20A、25A、32A、40A

Rated Leakage Operating lrn (mA)

30mA

Rated Leakage Breaking Time

15mA

Poles

1P+N

Rated breaking capacity lcu(A)

3000A

Operating time

≤0.1s

Tripping characteristic

Table 2

Mechanical life & Electrical life

Mechanical life:4000 ;Electrical life: :2000

Nominal cross section area S (mm2)

10mm2

Pollution degree

Protection class

IP20

Overvoltage category


Table 2 Tripping characteristic

Type

Test current

Initial situation

Tripping time

Test result

Remarks

B, C, D

1.13In

Cold

t≤1h

Not-tripping


B, C, D

1.45In

Following No.1 test

t<1h

Tripping

Current stablely raised to specified value in 5s

B, C, D

2.55In

Cold

1s<t<60s(≤32A)
1s<t<120s(>32A)

Tripping


B
C
D

3In
5In
10In

Cold

t≤0.1s

Not-tripping

Switch on the power supply by closing the auxiliary switch

B
C
D

5In
10In
20In

Cold

t<0.1s

Tripping

Switch on the power supply by closing the auxiliary switch


Note: The terminology “Cold state” means that the test is performed at the base calibration temperature with no load prior to the test.


4. Working and the installing condition

4.1 Ambient max temperature is no more than +40℃, minimum temperature is not less than -5℃. No more than +35℃ within 24 hours;
4.2 Altitude is no more than 2000m;
4.3 When the highest temperature reaches 40℃ the air relative humidity of the installing place can't exceed 50%, when in the low temperature it will have the relative higher humidity. When the average largest relative humidity in the most humiddest it is month no more than 90%, then the monthly-average temperature is no more than 25℃. We must take measure of the dew in the surface of the product due to the temperature;
4.4 Installation conditions: Any direction of the outer magnetic field of the installation site should not exceed 5 times than earth's magnetic field; residual current operated circuit breaker should be mounted vertically, all places inclination no more than 5 °,power position above the handle , the installation place should be no significant impact and vibration.


5. Appearance and installing size (mm)