1. Application

RCCB are applying to the circuit of Ac50/60Hz,230V single phase, 400V three phases , a rated current 16 -100A. and adapted for industrial mining enterprise, trade building, commerce and family. Mainly prevent electric fire and personal casualty accident caused by personal electric shock or leakage of electrified wire netting.本产品符合标准:GB16916.1及IEC61008-1

Standard Number:GB16916.1,IEC61008-1.


2. Type designation

3. Technical data

Model

Versions

Rated voltage(v) :

230/400V~

Rated current(A) :

25、32、40、63、80、100

Rated Leakage Operating lrn

0.03、0.1、0.3

lrno

0.5In

Poles :

2、4

Rated residual making and breaking capacity lr m

1000A

Maximum breaking time of the residual current operating

Mark 2

Mechanical life & Electrical life:

1000

2000

Pollution

3

Protection

IP20

Overvoltage

Mark 2 Maximum breaking time of the residual current operating(s)

Type

mA

I(n)

2I(n)

5I(n)

Non delay

0.1~

0.06

0.04


4. Working and the installing condition

4.1 : Ambient max temperature is no more than +40℃, minimum temperature is not less than -5℃. No more than +35℃ within 24 hours;

4.2 : altitude is no more than 2000m;

4.3 : when the highest temperature reaches 40℃ the air relative humidity of the installing place can't exceed 50%, We must take measure of the dew in the surface of the product due to the temperature.

5. Overall and mounting dimensions (mm)
DOWNLOAD