1. Application

miniature circuit breakers are mainly used in AC 50Hz circuit with rated voltage 230V/400V, rated current up to 63A or less, protection of control circuit against short circuit and overload current fault. And also have circuit control and isolation function. This circuit breaker is mainly used in all kinds of places such as industry, commerce, high-rise building and civil residence.

Product Standard : GB10963.1


2. Type designation


3. Technical data

Model

Versions

Rated voltage(v)

230V~(1P)、400V~(2P/3P/4P)

Rated current(A)

10、16、20、25、32、40、50、63

Poles :

1P、2P、3P、4P

Rated breaking capacity(A ) :l

6000A

Mechanical life & Electrical life:

6000&4000

Nominal cross section area S (mm2):

3.5N

Pollution Degree:

2

Protection class:

IP20

Overvoltage category :

Tripping characteristic

Mark 2


Mark 2 : Tripping characteristic (temperature 30℃)

Model

Tripping Characteristic

Test current

Initial situation

Tripping time

Test result

Remarks

A

B、C、D

1.13In

Cold

t≤1h

Not-tripping

Current stablely raised to specified value in 5s

B

B、C、D

1.45In

Following No.1 test

t≤1h

C

B、C、D

2.25In

Cold

1s<t<60s(ln≤32A) 1s<t<120s(ln>32A)

Switch on the power supply by closing the auxiliary switch


D

B、C、D

3In、5In、10In

Cold

t≤1hs


Not-tripping


Switch on the power supply by closing the auxiliary switch

E

B、C、D

5In、10In、20In

Cold

t≤1hs


tripping


Remark: "cold" means without load before test at the base of the calibration temperature.


4. Overall and mounting dimensions (mm)

Mark 3: Appearance and installing size

Poles

L(mm)

1P

17.8±0.20

2P

35.6±0.40

3P

53.4±0.60

4P

71.2±0.80


6. Certificate