1. Application
miniature circuit breaker can be used for equipment protection in power distribution system, protection of control circuit against short-circuit and overload current faults. And also have circuit control and isolation functions. The rated breaking capacity is 10000A.
2. Type designation
3. Technical data
Model |
Versions |
Rated voltage(v) |
230V(1P)、400V(2~4P) |
Rated current(A) |
63A、80A、100A |
Poles : |
1P、2P、3P、4P |
Rated breaking capacity(A) : |
Icu=10000A、Ics=7500A |
Uimp(V) |
8000V |
Tripping characteristic: |
Mark 2 |
Mechanical life & Electrical life: |
8500&1500次(operation frequency:120/h) |
Nominal cross section area S (mm2): |
Mark 3 |
Pollution Degree: |
2 |
Protection class: |
IP20 |
Overvoltage category : |
Ⅱ&Ⅲ |
Mark 3: Tripping characteristic (temperature 30℃) :
Model |
Rated current(A)
|
Initial situation |
Test current
|
Tripping time
|
Remarks |
a |
1.05In
|
Cold
Following No.1 test
|
t≤1h(In≤63A)
t≤2h(In≥63A)
|
Not-tripping
|
|
b |
1.3In
|
Cold
|
t<1h(In≤63A)
t<2h(In≥63A)
|
tripping
|
Current stablely raised to specified value in 5s
|
c |
2In
|
Cold
|
0<t<300s
|
tripping
|
|
d |
8In
|
Cold
|
t≤0.2s
|
Not-tripping
|
Switch on the power supply by closing the auxiliary switch
|
e
|
12In
|
Cold
|
t≤0.2s
|
tripping
|
Rated current(A) |
Nominal cross section area S(mm²)) |
|
63 |
16 |
|
80 |
25 |
|
100 |
35 |
4 Working and the installing condition.
4.1 : Ambient max temperature is no more than +40℃, minimum temperature is not less than -5℃. No more than +35℃ within 24 hours;
4.2 : altitude is no more than 2000m;
4.3 : when the highest temperature reaches 40℃ the air relative humidity of the installing place can't exceed 50%, when in the low temperature it will have the relative higher humidity. When the average largest relative humidity in the most humiddest it is month no more than 90%, then the monthly-average
temperature is no more than 25℃. We must take measure of the dew in the surface of the product due to the
temperature;
4.4 Installation conditions
Any direction of the outer magnetic field of the installation site should not exceed 5 times than earth's magnetic field; residual current operated circuit breaker should be mounted vertically, all places inclination no more than 5 °,power position above the handle , the installation place should be no significant impact
and vibration
5. Overall and mounting dimensions (mm)
Poles : |
a |
b |
1P
|
66±0.64 |
76±0.5
|
2P-4P
|
72±0.64 |
75±0.64
|
6. Certificate